Troubleshooting
FAT errors – error codes F01...F10
486
Error message
Cause(s)
Remedy
F07
Wrong area NV pointer
The start address of the non-volatile data is
outside the permitted area.
Possible cause:
Unacceptable interference on the 24 V power
supply during the storage operation of the data in
the flash device.
F01
F08 FAT
memory
An error occurred during the storage of the FAT.
Possible cause:
Unacceptable interference on the 24 V power
supply during the storage operation of the data in
the flash device.
F01
F09
NV field storage
An error has occurred during the storage of the
non-volatile data.
Possible cause:
Unacceptable interference on the 24 V power
supply during the storage operation of the data in
the flash device.
►
Repeat
command.
F10
General NV mirroring
An error has occurred during the change to the
mirror range of the non-volatile data.
Possible cause:
Unacceptable interference on the 24 V power
supply during the storage operation of the data in
the flash device.
►
Repeat
command.