Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Troubleshooting
AS-i system errors – error codes E10...E32
482
16.2
AS-i system errors – error codes E10...E32
6024
Menu operation interrupted.
Error message superposes the menu screen.
Error message only disappears after the following actions:
1. Error removed AND
2. Error message acknowledged with the right function key.
Error message
Cause(s)
Remedy
E10
Slave not activated
The slave was detected in the system but not
activated by the master.
Detected slave profile does not correspond to the
projected slave profile and the master is in the
"protected mode".
►
Check slave profile:
[Menu] > [Slave Info]:
Display slave data (
→
page
)
►
Connect slave with the right profile.
►
Reproject
slaves:
[Menu] > [Quick Setup]:
Finish configuration (
→
page
E11
Slave not present
Slave present in the "List of projected slaves" LPS
but not detected on the AS-i master.
►
Check slave connections.
►
Connect slave again.
E12
Slave not projected
The slave was detected on the AS-i bus but is
missing in the "List of projected slaves" LPS.
►
Reproject
slaves:
[Menu] > [Quick Setup]:
Finish configuration (
→
page
E13
Peripheral fault detected
Peripheral fault detected on at least one
connected slave.
Display of the list of slaves with peripheral
fault (LPF) (
→
page
Display of slave with peripheral fault
(
→
)
E14
Safety slave alert
Error message not active at present.
E15
Analogue protocol error
Error message not active at present.
E20
AS-i voltage error
The master is in the "Protected mode" and detects
that the AS-i voltage supply is not greater than
28 V.
The message is only generated if at least one
slave is projected.
►
Check AS-i voltage supply on the master
and replace - if necessary
E21
No slave detected
The master is in the "Protected mode" and detects
that no slave is connected to the AS-i bus.
The message is only generated if at least one
slave is projected.
►
Check slave connections.
►
Check AS-i line.
E22
Slave 0 detected
The master is in the "Protected mode" and detects
a slave with the address 0 on the AS-i bus.
This message is only generated if the profile of
the missing slave on the AS-i bus is identical to
the profile of the slave with the address 0.
►
Switch master to the operating mode
"Projection mode":
How to switch the operating modes for
the AS-i master. (
→
page
E23
Slave 0 has wrong profile
The master is in the "Protected mode" and detects
a slave with the address 0 on the AS-i bus.
This message is only generated if the profile of
the missing slave on the AS-i bus is not identical
with that of the slave with the address 0.
►
Check and replace slave.
►
Reproject
slaves:
[Menu] > [Quick Setup]:
Finish configuration (
→
page