ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Function
Introduction AS-i data
36
IO code
(hex)
ID code
(hex)
ext. ID
code
2
(hex)
Meaning
7 2
x
extended slave profile for the transmission of 6...18-bit signals;
extended analogue profile for combined transaction type 1;
was replaced by S-7.4
7 3
x
slave profile for 16-bit transmission with integrated support in the master;
integrated analogue profile for combined transaction type 1
(
Extended ID code 2 for analogue slaves with profile 7.3.x (
→
page
7
3
5
2 analogue outputs of 16 bits each (e.g. I/O module AC2618)
7
3
6
4 analogue outputs of 16 bits each (e.g. I/O module AC2518)
7
3
C
1 analogue input of 16 bits (e.g. sensor PPA020)
7
3
D
2 analogue inputs of 16 bits each (e.g. I/O module AC2616)
7
3
E
4 analogue inputs of 16 bits each (e.g. I/O module AC2516)
7 4
x
extended slave profile for 16-bit transmission with integrated support in the master;
integrated extended analogue profile for combined transaction type 1
(
Extended ID code 2 for analogue slaves with profile 7.4.x (
→
page
7 4
C
RFID identification system for writing and reading RFID tags
15-bit data + 1-bit messages (e.g. DTA100)
7
A
x
slave operates in the "extended addressing mode" (B slave or A/B slave)
7 A
5
slave operates in the "extended addressing mode" (B slave or A/B slave)
combined slave; supports combined transaction type 2
7 A
7
slave operates in the "extended addressing mode" (B slave or A/B slave)
4 binary 4 binary outputs
7 A
8
slave operates in the "extended addressing mode" (B slave or A/B slave)
1 channel for combined transaction type 4
7 A
9
slave operates in the "extended addressing mode" (B slave or A/B slave)
dual channel for combined transaction type 4
7 A
A
slave operates in the "extended addressing mode" (B slave or A/B slave)
8 binary 8 binary outputs
7 A
E
slave operates in the "extended addressing mode" (B slave or A/B slave);
dual sensor with actuator interface (e.g. sensor AC2317);
2 binary 2 binary outputs
7
B
x
safety slave with non-safe outputs
7 B
0
safety slave with non-safe outputs;
2 safe binary inputs (e.g. I/O module AC005S)
7 B
E
safety sensor with non-safe outputs;
2 safe binary inputs AND
2 safe binary outputs AND
2 non-safe (relay) outputs (e.g. I/O module AC009S)
7
D
x
device for motor control (electromechanical)
7
D
0
electromechanical motor control with open sub-profile
7
D
1
electromechanical direct starter
7 D
2
electromechanical
reverser
7 D
3
electromechanical
direct starter with brake
7
D
4
electromechanical reverser with brake
7 D
5
electromechanical
direct starter with accessories
7
D
6
electromechanical reverser with accessories
7
E
x
device for motor control (electronic)
7
E
0
electronic motor control with open sub-profile
7
E
1
electronic direct starter