ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Acyclic services for Profibus DPV1
Acyclic command in the DPV1 command channel
356
Response from device to fieldbus master in the normal case
: Safety-at-Work monitor has triggered
Word no.
Value [hex.]
Meaning
1
076F
07 = reflected user ID
6F = command status is "done" (no error)
2
001F
reflected command number
3
001E
reflected command data
4
2211
2x = output circuit 1 red;
x2 = invalid,
word 5;
11 = protective operation, output circuit 1 off
5
0003
00 = OSSD2 green
03 = OSSD1 not green, provides 3 modules which are not green
6
0421
04 = red permanently lit
21 = module 33
7
0422
04 = red permanently lit
22 = module 34
8
0423
04 = red permanently lit
23 = module 35
9…11 xxxx
not relevant, because low byte of 5th word = 03
3 modules relevant
12…17 xxxx
not relevant, because high byte of 5th word = 00
green, no module relevant
18
0000
reflected field number
19 xxxx
not
changed
Response from device to fieldbus master in case of a fault
Word no.
Value [hex.]
Meaning
1
076B
07 = reflected user ID
6B = error during command execution
2
001F
reflected command number
3
0011
error code=11: no slave with the profile S-7.F.F on the slave address
4…19 xxxx
not
changed