ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
The fieldbus command channel (module 11)
Module 11, command 15dec (0Fhex) – read AS-i cycle counter
117
6.14.3
Example: read AS-i cycle counter of AS-i master 1
4787
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1 400F
(master no.
1 * 64
)
= 64
dec
=
40
hex
0F = command 15
2 0000
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1 400F
copy of the request
command processed, no error occurred
2
4CA
cycle counter = 04CA
hex
= 1 226
dec
Since the last power on of the device, 1 226 cycles have been performed in the AS-i
master 1.