ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
60
Example for module 10
10641
Task:
Channel 4 (according to the labelling on the unit) of the analogue output slave with the AS-i
address 12 on master 1 is to be set to the value 5000.
Solution:
as follows:
Request from host to device
Word 1:
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Value
0
1
0
0
1
1
0
0 0 0 0 0 0 0 1
1
Description
master 1
slave 12
channel 4
single slave
Word 2: analogue value = 5000
Response from device to host
Word 1: Copy of word 1 of the request
Word 2: Copy of word 2 of the request