ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
75
Examples for module 14
10663
Task 1:
The value 12 is specified for module 14. The setting for channels per slave is 1. What is the
highest AS-i slave address whose data can be transmitted with this setting and how many words
are transmitted in total?
Solution:
The highest AS-i slave address is 12. 24 words are transmitted.
Table
Input data for 1 channel per slave
(
→
page
).
Task 2:
To which minimum value must module 14 be set so that the data of the analogue input slave with
the AS-i address 10 can be read (setting 4 channels per slave)? In which word within the range
can the data of channel 3 of the said slave be found?
Solution:
The value to be set for module 14 is 10. The data of slave 10, channel 3 can be found in word 38
of the range.
Table
Input data for 4 channels per slave
(
→
page
).