15BError messages
103BProcess error: error codes E10...E30 (AS-i system)
16-4
16.2
Process error: error codes E10...E30 (AS-i system)
•
Error message appears instead of the start screen.
•
No interruption of the menu operation.
•
Exclamation mark flashes in the text/graphics display in the middle of the line
at the bottom (only if projection mode is deactivated)
•
The error message disappears again as soon as the error has been corrected.
Error message
Cause(s)
Solution
E10
Slave not activated
The slave was detected in the system
but not activated by the master.
Detected slave profile does not corre-
spond to the projected slave profile and
the master is in the "protected mode".
►
Check slave profile:
"Menu" > "Slave Info"
→
page 13-48, chapter 13.22 "Display
►
Connect slave with the right profile
►
Project slaves again:
"Menu" > "Quick Setup"
→
page 11-15, chapter "End configura-
E11
Slave not present
Slave present in the "List of projected
slaves" LPS but not detected by the
AS-i master
►
Check connections of the slave
►
Connect slave again
E12
Slave not projected
The slave was detected on the AS-i bus
but is missing in the "List of projected
slaves" LPS
►
Project slaves again:
"Menu" > "Quick Setup"
→
page11-15, chapter "End configura-
E13
Peripheral fault detected on at least one
connected slave
→
page 13-11, chapter 13.6 "Display of
slaves with peripheral fault (list)"
→
page 13-14, chapter 13.7 "Display
E14
Safety slave signals alarm
Error message not active at present
E15
7.3 Analogue protocol error
Error message not active at present
E20
AS-i voltage error
The master is in the "Protected mode"
and detects that the AS-i voltage supply
is not greater than 28 V.
The message is only generated if at
least one slave is projected.
►
Check AS-i voltage supply on the
master and – if necessary – replace
E21
No slave detected
The master is in the "Protected mode"
and detects that no slave is connected
to the AS-i bus.
The message is only generated if at
least one slave is projected.
►
Check slave connections
►
Check AS-i line
Содержание Ecomat 300 AC1307
Страница 10: ......
Страница 14: ......
Страница 16: ......
Страница 18: ......
Страница 30: ......
Страница 32: ......
Страница 62: ......
Страница 96: ......
Страница 114: ......
Страница 175: ...13BScale drawing 14 1 14 Scale drawing 107 97 86 LED 62 2 1 3 Figure dimensions of the controllere ...
Страница 176: ......
Страница 180: ......
Страница 206: ......
Страница 208: ......
Страница 215: ......