15BError messages
105BSystem errors: error codes F21...F30 (FAT errors)
16-10
Error message
Cause(s)
Solution
F26
Invalid identifier of the remanent data
detected
The field ID of the remanent data con-
tains an invalid value.
Possible cause: impermissible interfer-
ence on the 24V power supply during
the storage operation of the data in the
flash device.
►
ditto
F27
Pointer to remanent data in the wrong
area
The start address of the remanent data
is outside the permitted area.
Possible cause: impermissible interfer-
ence on the 24V power supply during
the storage operation of the data in the
flash device.
►
ditto
F28
Storage of the FAT failed
An error has occurred during the stor-
age of the FAT.
Possible cause: impermissible interfer-
ence on the 24V power supply during
the storage operation of the data in the
flash device.
►
ditto
F29
Storage of the remanent data failed
An error has occurred during the stor-
age of the remanent data.
Possible cause: impermissible interfer-
ence on the 24V power supply during
the storage operation of the data in the
flash device.
►
Repeat the command
F30
Change to the mirror range of the re-
manent data failed
An error has occurred during the
change to the mirror range of the rema-
nent data.
Possible causes: impermissible interfer-
ence on the 24V power supply during
the storage operation of the data in the
flash device.
►
Repeat the command
Содержание Ecomat 300 AC1307
Страница 10: ......
Страница 14: ......
Страница 16: ......
Страница 18: ......
Страница 30: ......
Страница 32: ......
Страница 62: ......
Страница 96: ......
Страница 114: ......
Страница 175: ...13BScale drawing 14 1 14 Scale drawing 107 97 86 LED 62 2 1 3 Figure dimensions of the controllere ...
Страница 176: ......
Страница 180: ......
Страница 206: ......
Страница 208: ......
Страница 215: ......