96BSet output values
13-51
13.23
Set output values
For testing it might be useful to set the value of an output without being affected by
the PLC program. The controllere helps you.
WARNING
The output values remain unchanged
Risk of personal injury! Risk of material damage to the machine/plant! After chang-
ing the slave outputs the output values remain unchanged.
The output values only change in the following cases:
•
Manual new setting of the outputs via Slave Setup
•
Starting the PLC program – the program processes the outputs
•
Switch
the
controllere off and on again
►
Secure the concerned area.
►
Only trained personnel must manually set the outputs.
►
Switch the outputs off again immediately after the end of the test.
i
Tip
Changes to the outputs are not effective in the following cases:
•
The PLC is in the RUN mode (LED [PLC RUN] lights).
•
AND: The corresponding outputs are processed by the PLC.
•
Changes of digital outputs on analogue modules.
•
Changes of analogue outputs on digital modules.
►
Switch PLC to the operating mode STOP
→
page 10-4, chapter "How are the operating modes for the PLC changed?"
LED [
PLC RUN
] flashes
i
Tip
Password level 2 required
→
page 11-23, chapter "Password setting"
M
M
E
E
N
N
U
U
0
U
U
S
S
E
E
R
R
1.
►
Press the [
MENU
] button
Содержание Ecomat 300 AC1307
Страница 10: ......
Страница 14: ......
Страница 16: ......
Страница 18: ......
Страница 30: ......
Страница 32: ......
Страница 62: ......
Страница 96: ......
Страница 114: ......
Страница 175: ...13BScale drawing 14 1 14 Scale drawing 107 97 86 LED 62 2 1 3 Figure dimensions of the controllere ...
Страница 176: ......
Страница 180: ......
Страница 206: ......
Страница 208: ......
Страница 215: ......