14BTechnical data
98BGeneral data
15-1
15
Technical data
15.1
General data
Operating voltage
20...30 V DC (PELV)
Current consumption
< 0.5 A (depending on the implemented options)
Operating temperature
0...+60 °C
Storage temperature
-20...+70 °C
Protection to DIN 40050
IP 20
Housing material
aluminium, galvanised steel
Fixing
on Din rail 35 mm
Housing dimensions
106.3 x 85.5 x 123.6 mm
15.2
Data AS-i master
Number of AS-i masters
1 (standard) or 2 (option)
AS-interface profile
M3 to version 2.1
AS-interface voltage
26.5...31.6 V (special AS-i power supply)
Current consumption from
AS-i
0.01 A / master
Microcontroller
Infineon C1610 microcontroller
Supported V2.1 features
•
A/B slaves
•
Peripheral fault detection
•
Analogue Plug+Play (profile 7.3 / 7.4)
•
Extended ID codes
Other features
•
AS-i cycle counter
•
Communication error counter per slave
•
Configuration error counter
•
Change to the protected mode without reset-
ting the AS-i system