ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Operating and display elements
Diagnostic LEDs
93
Diagnostic LEDs
LED
colour
LED out
LED lit
LED flashes
ASI1 [PWR/COM]
AS-i bus 1:
P
o
w
e
r
Com
munication
Green
No supply for AS-i
bus 1
AS-i supply available;
at least 1 slave
detected on the bus
AS-i supply available;
no slave correctly
detected on the bus
ASI1 [PROJ]
AS-i bus 1:
Proj
ection
Yellow Operating mode active
Configuration mode
active; configuration
monitoring deactivated
Configuration mode
active; changeover to
protected mode not
possible because a
slave with the address
0 is connected
ASI1 [CONF/PF]
AS-i bus 1:
Conf
iguration
P
eriphery
F
ailure
Red
Configuration and
periphery ok
Projected and current
configuration do not
match
Periphery fault
detected on at least
one connected slave
ASI2 [PWR/COM]
AS-i bus 2:
P
o
w
e
r
Com
munication
Green
No supply for AS-i
bus 2
AS-i supply available;
at least 1 slave
detected on the bus
AS-i supply available;
no slave correctly
detected on the bus
ASI2 [PROJ]
AS-i bus 2:
Proj
ection
Yellow Operating mode active
Configuration mode
active; configuration
monitoring deactivated
Configuration mode
active; changeover to
protected mode not
possible because a
slave with the address
0 is connected
ASI2 [CONF/PF]
AS-i bus 2:
Conf
iguration
P
eriphery
F
ailure
Red
Configuration and
periphery ok
Projected and current
configuration do not
match
Periphery fault
detected on at least
one connected slave
[24V PWR]
Green
No 24 V operating
voltage
24 V operating voltage
available
---
[PLC RUN]
Yellow
Controllere operates
as a gateway
PLC program in the
controllere active
PLC program in the
controllere stopped
[EthNet]
yellow
no communication in
the Ethernet
LED flashes for each data package