Function
Introduction AS-i data
38
Extended ID code 2 for analogue slaves with profile 7.4.x
The extended ID code 2 is used to specify complex slaves.
Structure slave profile = S-7.3.[ext.ID code2]
Bit 3
(8
h
)
Bit 2
(4
h
)
Bit 1
(2
h
)
Bit 0
(1
h
)
Description
0
0
1-channel slave
0
1
2-channel slave
1
0
4-channel slave
1
1
4-channel slave (if slave has no extended ID code)
0
0
0
0
4 binary 4 binary outputs
0
Output slave
1
Input slave
The ID code 2 results from a combination of the options stated above.
Valid combinations IO code / ID code / extended ID code 2
Structure slave profile = S-[IO code].[ID code].[ext.ID code2]
x = any value (0…F)
IO code (hex)
ID code
(hex)
Ext. ID
code 2
(hex)
Description
0…E
not: 9, B, D
0
x
Binary I/O connections for sensors and actuators
0, 3, 8
1
x
1 or 2 binary sensors or actuators with 2 signals each (dual-signal devices)
0
1
x
4 binary inputs for 2 dual-signal sensors
0…E
not: 2, A
A
x
Slave operates in the "extended addressing mode" (B slave or A/B slave)
0
A
E
Slave with extended address function:
4 binary inputs for 2 dual-signal sensors (e.g. I/O module AC2250)
0
B
x
Slave corresponds to "Safety at Work"
0…E
F
x
Manufacturer-specific device (cannot be replaced by other products)
1
1
x
Single sensor with remote setting:
3 binary 1 binary output (e.g. sensor OC5226)
3
1
x
2 binary inputs for 1 dual-signal sensor AND
2 binary outputs for 1 dual-signal actuator
3
A
x
Slave with extended address function
3
A
1
Slave with extended address function:
2 binary 1 binary output
3
A
2
Slave with extended address function:
4 binary inputs
6
0
x
Quick combined transmission type 5 of 8, 12 or 16 data bits by using 2, 3 or 4 slave
addresses in a slave
7
0
F
Motor starter 2I + 2O (e.g. ZB0032)
7
0
E
4 binary 4 binary outputs (e.g. I/O module AC2251)
7
1
x
Interface for the transmission of 6...18-bit signals;
analogue profile for combined transmission type 1;
was replaced by S-7.3
7
2
x
Extended slave profile for the transmission of 6...18-bit signals;
extended analogue profile for combined transmission type 1;
was replaced by S-7.4
7
3
x
Slave profile for 16-bit transmission with integrated support in the master;
integrated analogue profile for combined transmission type 1
(
Extended ID code 2 for analogue slaves with profile 7.3.x
7
3
5
2 analogue outputs of 16 bits each (e.g. I/O module AC2618)
7
3
6
4 analogue outputs of 16 bits each (e.g. I/O module AC2518)
7
3
C
1 analogue input of 16 bits (e.g. sensor PPA020)
7
3
D
2 analogue inputs of 16 bits each (e.g. I/O module AC2616)
7
3
E
4 analogue inputs of 16 bits each (e.g. I/O modulel AC2516)