Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Set-up
Configuration
134
11.2.4
Finish configuration
NOTE
Now all slaves are present on the bus with the correct address.
But the error message ("!") keeps on flashing and the LED [CONF/PF] lights?
Cause: The controllere detected all slaves on the bus but the slaves are not yet - at least not all
slaves - in the "list of projected slaves" LPS.
This means: The error message "Config. Error" is displayed as long as there is a difference between
the detected and configured slaves.
Help: In the mode "Quick Setup" enter all detected slaves in the configuration list by pressing a key.
Password level 1 required
[MENU] > [Slave Lists] > select master > [Detected Slaves]
1. E25 ASi1
Config. Error
>
The display on the left appears instead of the
ifm
start screen:
"Config. Error"
► Press the key [MENU]
M
M
E
E
N
N
U
U
1/2
▲
!
▼
U
U
S
S
E
E
R
R
2. PLC Setup
Slave Lists
Address Slave
>
The controllere shows the last used menu item
► Press [▲] to scroll to [Slave Lists]
Reason: Check the configuration made so far in the list of detected
slaves LDS.