ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Error description
Boot errors: error codes B00...B11
241
Error message
Cause(s)
Remedy
B07
Number of master mismatch
When the version releases of the
masters were checked some invalid
information was received.
Possible cause: Hardware fault.
► Replace controllere and project
again.
B08
Exec. of PLC blocked by user
When the device was started the
automatic start of the PLC program was
disabled by the user. The left function
key of the device was pressed during
power-on.
► Release function key during power-
on.
or:
► No action because this is
requested.
B09
Reserved
––
B10
Master 1 firmware obsolete
The AS-i master firmware does not
contain functions required for the RTS
operating system.
► Updating the AS-i master firmware
to the required minimum version.
B11
Master 2 firmware obsolete
→ B10
→ B10