ifm
Basic Device Manual AS-i ControllerE M4 Target V15
2015-10-30
Error description
Boot errors: error codes B00...B11
240
16.1
Boot errors: error codes B00...B11
Menu operation interrupted.
Error message superposes menu screen.
Error message only disappears after the following actions:
1. Error removed AND
2. error message acknowledged with the right function key.
Error message
Cause(s)
Remedy
B00
Controller Boot error
After power-on of the device, an error
was found during initialisation of the
individual device components.
For further details please refer to the
following error messages.
► Check further error messages.
B01
Master initialization
Failed initialisation of the masters.
Possible causes:
Unacceptable interference on the
24 V power supply.
Unacceptable interference on the
AS-i power supply.
Unacceptably high electrostatic
charges and electromagnetic fields
in close proximity of the device.
► Grounding the device via the rail.
► Connection of the FE terminal to
the machine ground.
► Use of a switched-mode power
supply to supply the device.
B02
Master2 initialization
→ B01
B03
General FAT failure
An error was found in the data field of
the "File Allocation Table" FAT.
► Check further error messages.
B04
Only one master detected
The operating system can only detect 1
master in the controllere although
communication with 2 masters must be
possible.
Possible causes: hardware fault.
► Replace controllere and project
again.
B05
Two masters detected
The operating system can detect 2
masters in the controllere although
communication with only 1 master is
allowed.
Possible cause: hardware fault.
► Replace controllere and project
again.
B06
Fieldbus type not expected
During the automatic detection of the
integrated fieldbus no enabled fieldbus
module could be detected.
Possible cause: hardware fault.
► Replace controllere and project
again.