CAN1_BAUDRATE
651
Unit type = function block (FB)
Unit is contained in the library
ifm_CR0301_Vxxyyzz.LIB
Symbol in CODESYS:
>
Description
654
CAN1_BAUDRATE sets the transmission rate for the bus participant.
► To do so, the corresponding value in kbits/s is entered at the input BAUDRATE.
NOTICE
Please note for CR250n, CR0301, CR0302 and CS0015:
The EEPROM memory module may be destroyed by the permanent use of this unit!
► Only carry out the unit
once
during initialisation in the first program cycle!
► Afterwards block the unit again with ENABLE = FALSE!
The new baud rate will become effective on RESET (voltage OFF/ON or soft reset).
ExtendedController:
In the slave module, the new baud rate will become effective after voltage
OFF/ON.
>
Parameters of the inputs
655
Parameter
Data type
Description
ENABLE
BOOL
TRUE (in the 1st cycle):
Adopt and activate parameters
else:
this function is not executed
BAUDRATE
WORD := 125
Baud rate [kbits/s]
valid = 20, 50, 100, 125, 250, 500, 1000