16
ifm
Programming Manual
ecomatmobile
CabinetController (CR0301) Runtime System V05
2016-04-21
System description
Hardware description
>
If runtime system / application is running
3928
then the following tests are cyclically carried out:
>
Triggering of the watchdog (100 ms)
Then continuous program check watchdog
>
Continuous temperature check
In case of a fault: system flag ERROR_TEMPERATURE = TRUE
>
Continuous voltage monitoring
In case of a fault: system flag ERROR_POWER = TRUE or ERROR_VBBR = TRUE
>
Continuous CAN bus monitoring
>
Continuous system data monitoring:
- program loaded
- operating mode RUN / STOP,
- runtime system loaded,
- node ID,
- baud rate of CAN and RS232.
>
In the operating mode RUN:
Cyclical I/O diagnosis:
- short circuit,
- wire break,
- overload (current) of the inputs and outputs,
- cross fault (only for SafetyController).
>
If the TEST pin is not active
3929
>
Write protection for system data in FRAM ¹), e.g.:
• runtime system loaded,
• calibration data.
Implemented via hardware and software.
>
Write protection for application program (in the flash memory)
>
DEBUG mode
¹) FRAM indicates here all kinds of non-volatile and fast memories.
>
One-time mechanisms
3930
>
CRC monitoring during download or upload.
>
It must be checked that the runtime system and the application are assigned to the same device.