Parameters of the inputs
2067
Parameter
Data type
Description
CANOPEN_LED_STATUS
BOOL
(input not available for PDM devices)
TRUE:
the status LED of the controller is switched to the
mode "CANopen":
flashing frequency 0.5 Hz = PRE-OPERATIONAL
flashing frequency 2.0 Hz = OPERATIONAL
The other diagnostic LED signals are not changed by this operating
mode.
GLOBAL_START
BOOL
TRUE:
All connected network participants (slaves)
are started simultaneously during network initialisation
(
state OPERATIONAL).
FALSE:
The connected network participants are started
one after the other.
CLEAR_RX_OVERFLOW_FLAG
BOOL
FALSE
TRUE (edge):
Clear error flag RX_OVERFLOW
else:
this function is not executed
CLEAR_RX_BUFFER
BOOL
FALSE
TRUE (edge):
Delete data in the receive buffer
else:
this function is not executed
CLEAR_TX_OVERFLOW_FLAG
BOOL
FALSE
TRUE (edge):
Clear error flag TX_OVERFLOW
else:
this function is not executed
CLEAR_TX_BUFFER
BOOL
FALSE
TRUE (edge):
Delete data in the transmit buffer
else:
this function is not executed
CLEAR_RESET_FLAGS
BOOL
FALSE
TRUE (edge):
Clear flag RESET_NODE
Clear flag RESET_COM
else:
this function is not executed
CLEAR_OD_CHANGED_FLAGS
BOOL
FALSE
TRUE (edge):
Clear flag OD_CHANGED
Clear flag OD_CHANGED-_INDEX
else:
this function is not executed