A-58
A5
A5
HTML VARIAbLES
The webserver in the 9009 and 9099 includes generic HTML pages for control-
ling Watlow F4, EZ Zone and F4T Temperature Controllers. This appendix lists
the HTML substitution variables (%xx%) and replacement parameters (xxsp)
used on the pages and their respective Modbus registers. Register functions
are given in the respective Watlow Controller manual. Refer to ICS Applica-
tion Note AB80-5 for instructions on customizing and replacing the 9009 and
9099 html pages.
A5.1 F4.html
This page is for the Watlow F4 Controller
Variable
Description
Register Type
Temperature Humidity Variables
%input1%
Process 1 Temperature Reading
100 16-bit R
%input1sp%
Process 1 Temperature Setpoint
300 16-bit RW
input1sp
Process 1 Temperature Setpoint
300 16-bit RW
%degCon%
Displays °C units
901 16-bit RW
%degCoff%
Displays °F units
901 16-bit RW
degC
Radio Values 'On' and 'Off'
901 16-bit RW
%input2%
Process 2 Humidity Reading
104 16-bit R
%input2sp%
Process 2 Humidity Setpoint
319 16-bit RW
input2sp
Process 2 Humidity Setpoint
319 16-bit RW
%input3%
Process 3 Auxilary Input
108 16-bit R
Output Control Variables
%dout1on%
Displays Output 1 On
2000 16-bit RW
%dout1off%
Displays Output 1 Off
2000 16-bit RW
dout1
Radio Values 'On' and 'Off'
2000 16-bit RW
%dout2on%
Displays Output 2 On
2010 16-bit RW
%dout2off%
Displays Output 2 Off
2010 16-bit RW
dout2
Radio Values 'On' and 'Off'
2010 16-bit RW
%dout3on%
Displays Output 3 On
2020 16-bit RW
%dout3off%
Displays Output 3 Off
2020 16-bit RW
dout3
Radio Values 'On' and 'Off'
2020 16-bit RW
Содержание 9099
Страница 20: ...1 16 1 Figure 1 1 9009 Outline Dimensions ...
Страница 24: ...1 20 1 Figure 1 3 9099 Certificate of Compliance ...
Страница 54: ...3 8 3 Figure 3 1 Status Reporting Structure Flash Configuration Reset ...
Страница 94: ...3 48 3 This page left intentionally blank ...
Страница 100: ...4 4 6 This page is left intentionally blank ...
Страница 161: ...A 49 A4 Refer to the ErrorLogger utility for the error value definitions Error Meaning 0 No error ...