PIR-130-AC/DC User Manual
Ver. 1.4.0, 2020/07/28
71/93
2.28
@AARH
Description:
This command is used to read the current High Alarm limits for a specified module.
Syntax:
@AARH[CHKSUM](CR)
@
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
RH
The command to read the current High Alarm limits .
Response:
Valid Command:
!AA(Data)[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate that the command was valid
?
Delimiter character to indicate that the command was invalid
AA
The address of the responding module in hexadecimal format (00 to FF)
(Data)
A signed value representing the High Alarm limits in degrees Celsius in the format
xxx.xx. The valid range is +000.00 to +999.99.
There will be no response if the command syntax is incorrect, there is a communication error, or
there is no module with the specified address.
Examples:
Command: @03HI+090.50
Response:!03
Sets the High Alarm limits for module 03 to +90.5 degrees Celsius, and returns a
response indicating that the command was valid.
Command: @03RH
Response: !03+090.50
Reads the High Alarm limits for module 03, and returns a response indicating that the
command was valid, with a value of +090.50, which denotes that the High Alarm limits
is +90.5 degrees Celsius.
Содержание PIR-130-AC
Страница 1: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 1 93 PIR 130 AC DC User Manual ...
Страница 11: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 11 93 1 4 Wiring Connections PIR 130 AC PIR 130 DC ...
Страница 15: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 15 93 1 7 Hardware Overview Front Rear ...
Страница 37: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 37 93 Related Commands Section 2 4 AA6 ...