PIR-130-AC/DC User Manual
Ver. 1.4.0, 2020/07/28
7/93
1.2
Specifications
Model
PIR-130-AC
PIR-130-DC
PIR
Time-delay
Hardware: 8-step Switch-selectable (seconds): 6, 16, 33, 66, 131,
262, 524, 1049
Software: 16-step (seconds): 2, 4, 6, 8, 16, 33, 49, 66, 131, 262,
393, 524, 1049, 2097, 3146, 4194
LUX Control Level :
Hardware: 2 mode (Dawn and dust) / Software: 5-step
Detection Range
Distance: 4 meters Max.
Detection Field of View
360º; Diameter 8 meters Max.
Temperature Sensor
Measuring Range
-25 ~ +100 °C
Fire Alarm
65°C (Programmable)
Resolution
0.0625 °C
Accuracy
±2 °C
Relay Output
Channels
1
Type
Power Relay, Form C
Max. Load Current
NO: 10A@250VAC
NC: 6A@250VAC
Load Wattage
Incandescent Bulb: 1500 W Max.; Fluorescent Lamp 300 W Max.
RS-485 Interface
COM Port
RS-485
Transmission
Distance
(m)
Dependent on Baud Rate. For example, 1200 m Max. at 9600 bps.
Baud Rate (bps)
Softeare:1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Protocol
DCON, Modbus RTU
Node Address
Hardware:160 ~ 191 / Software:1 ~ 255
LED Indicators
LED Indicators
Yes,1 as Power/Communication Indicator. 1 as Alarm Indicator
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for Each Terminal, ±8 kV Air for Random Point
EFT (IEC 61000-4-4)
±4 kV for Power Line
Power Requirements
Содержание PIR-130-AC
Страница 1: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 1 93 PIR 130 AC DC User Manual ...
Страница 11: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 11 93 1 4 Wiring Connections PIR 130 AC PIR 130 DC ...
Страница 15: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 15 93 1 7 Hardware Overview Front Rear ...
Страница 37: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 37 93 Related Commands Section 2 4 AA6 ...