PIR-130-AC/DC User Manual
Ver. 1.4.0, 2020/07/28
67/93
2.25
@AAHI(Data)
Description:
This command is used to set the High Alarm limits for a specified module.
Syntax:
@AAHI(Data)[CHKSUM](CR)
@
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
HI
The command to set the High Alarm limits
(Data)
A signed value representing the High Alarm limits in degrees Celsius in the format
xxx.xx. The valid range is +000.00 to +999.99 degrees Celsius.
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate that the command was valid
?
Delimiter character to indicate that the command was invalid
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a communication error, or
there is no module with the specified address.
Examples:
Command: @01HI+086.00
Response:!01
Sets the High Alarm limits for module 01 to +86.00 degrees Celsius, and returns a
response indicating that the command was valid.
Command: @01RH
Response: !03+086.00
Reads the high alarm limits for module 01, and returns a response indicating that the
command was valid, with a value of +086.00, which denotes that the High Alarm limits
is +86.0 degrees Celsius.
Содержание PIR-130-AC
Страница 1: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 1 93 PIR 130 AC DC User Manual ...
Страница 11: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 11 93 1 4 Wiring Connections PIR 130 AC PIR 130 DC ...
Страница 15: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 15 93 1 7 Hardware Overview Front Rear ...
Страница 37: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 37 93 Related Commands Section 2 4 AA6 ...