PIR-130-AC/DC User Manual
Ver. 1.4.0, 2020/07/28
77/93
0: Inactive
00262
Enables or disables the high temperature alarm..
0: Disabled
1: Enabled
R/W
00263
Reads/sets the high temperature alarm type.
0: Momentary Alarm
1: Latch Alarm
R/W
00274
Enables or disables Buzzer activation for when the PIR Sensor is
triggered.
0: Disabled
1: Enabled
R/W
00305
Reads/sets the
high alarm status, write 1 to clear latched
high alarm
R/W
30226
Reads/sets the High alarm limits
R/W
30513
Reads/sets the PIR Relay Output On Time for when the PIR
Sensor is triggered in hexadecimal format. The valid range is 00
to 0F.
Hex
Secs
Hex
Secs
Hex
Secs
Hex
Secs
00
2
01
4
02
6
03
8
04
16
05
33
06
49
07
66
08
131
09
262
0A
393
0B
524
0C
1049
0D
2097
0E
3146
0F
4194
R/W
30514
Reads/sets the Luminance Value for the PIR Sensor. The valid
range is 0 to 4, where.
0: Disabled
1: 100 Lux
2: 200 Lux
3: 500 Lux
4: 1000 Lux
R/W
30516
Reads/sets the Active Delay Time for the Relay Output in
milliseconds. The valid range is 0 to 0xBB8 (0 to 3000
milliseconds).
R/W
30517
Reads/sets Sensitivity value for the PIR Sensor. The valid range
is 0 to 9, where a lower value denotes a higher sensitivity.
R/W
Содержание PIR-130-AC
Страница 1: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 1 93 PIR 130 AC DC User Manual ...
Страница 11: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 11 93 1 4 Wiring Connections PIR 130 AC PIR 130 DC ...
Страница 15: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 15 93 1 7 Hardware Overview Front Rear ...
Страница 37: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 37 93 Related Commands Section 2 4 AA6 ...