2.21
~AADVV
Description:
This command is used to set the PIR Relay Output signal for a specified module to active or
inactive.
Syntax:
~AADVV[CHKSUM](CR)
~
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
D
The command to set the PIR Relay Output to active or inactive
VV
A two-digit hexadecimal value representing the status of the PIR Relay Output
signal. See below for details.
7
6
5
4
3
2
1
0
Reserved
OAS
Reserved
Key
Description
OAS
Specifies the status of the PIR Relay Output signal
0: An output value of 0 indicates that the relay is inactive
An output value of 1 indicates that the relay is active
1: An output value of 0 indicates that the relay is active
0:
An output value of 1 indicates that the relay is inactive
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate that the command was valid
?
Delimiter character to indicate that the command was invalid
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a communication error, or
there is no module with the specified address.
Содержание PIR-130-AC
Страница 1: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 1 93 PIR 130 AC DC User Manual ...
Страница 11: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 11 93 1 4 Wiring Connections PIR 130 AC PIR 130 DC ...
Страница 15: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 15 93 1 7 Hardware Overview Front Rear ...
Страница 37: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 37 93 Related Commands Section 2 4 AA6 ...