PIR-130-AC/DC User Manual
Ver. 1.4.0, 2020/07/28
12/93
1.5
DIP Switch Configuration
DIP [1]
Protocol:
Used to specify the communication protocol to be used by the module
ON:
DCON
OFF:
Modbus RTU (default)
DIP [2]
Configuration:
Used to specify the configuration settings for the module
ON:
Configure the module using DCON/Modbus commands
OFF:
Configure the module via DIP Switch (default)
DIP [3]
Address:
Used to specify the module address when DIP [2] is set to OFF
ON:
Use Rotary Switch positions 0 to F for node addresses 176 to 191
OFF:
Use Rotary Switch positions 0 to F for node addresses 160 to 175
(default)
DIP [4]
Mode:
Used to specify the Operating Mode
ON:
Operating in INIT mode
OFF:
Operating in Normal mode (default)
DIP [5]
PIR Operation:
Used to specify the Lux level at which the sensor will activate the light when
movement is detected.
ON:
The PIR Sensor will only detect motion when the Lux level is between
0 and 200
OFF:
The PIR Sensor will detect motion continuously (default)