PIR-130-AC/DC User Manual
Ver. 1.4.0, 2020/07/28
46/93
2.14
$AALC7C0NN
Description:
This command is used to set the PIR Relay Output ON Time for when the PIR Sensor is triggered
on a specific module.
Syntax:
$AALC70NN[CHKSUM](CR)
$
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
LC7
The command to set the PIR Relay Output ON Time for when the PIR Sensor is
triggered
C
The command to set the PIR Relay Output channel
0
Specifies the PIR Relay Output channel to be set, zero based.
Note that as there is only one PIR Sensor channel on the PIR-130 module, the only
valid value is 0.
NN
The command to set the PIR Relay Output ON Time for when the PIR Sensor is
triggered in hexadecimal format. This value will be stored in the EEPROM, and the
valid range is 00 to 0F.
NN
Seconds
NN
Seconds
NN
Seconds
NN
Seconds
00
2
01
4
02
6
03
8
04
16
05
33
06
49
07
66
08
131
09
262
0A
393
0B
524
0C
1049
0D
2097
0E
3146
0F
4194
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate that the command was valid
?
Delimiter character to indicate that the command was invalid
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a communication error, or
there is no module with the specified address.
Содержание PIR-130-AC
Страница 1: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 1 93 PIR 130 AC DC User Manual ...
Страница 11: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 11 93 1 4 Wiring Connections PIR 130 AC PIR 130 DC ...
Страница 15: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 15 93 1 7 Hardware Overview Front Rear ...
Страница 37: ...PIR 130 AC DC User Manual Ver 1 4 0 2020 07 28 37 93 Related Commands Section 2 4 AA6 ...