Intel® Server Compute Blade SBX82: Hardware Maintenance Manual and Troubleshooting Guide
error code numbers. You can view the BMC system event log from the Configuration/Setup Utility
menu by selecting Advanced Setup
>
Baseboard Management Controller (BMC) Settings
>
BMC System Event Log.
You can view additional information and error codes in plain text by viewing the SBCE
Management Module event log. This log can be accessed from the Configuration/Setup Utility menu
by selecting Error Logs option, or directly from the SBCE Management Module.
SCSI error codes
Temperature error messages
Error code
FRU/action
All SCSI Errors One or more of the
following might be causing the problem:
•
A failing SCSI device
(adapter, drive)
•
An improper SCSI configuration
•
Duplicate SCSI IDs in the same
SCSI chain
•
Verify that the SCSI devices are configured correctly.
✏
NOTE
See “System” on page 130 to determine which components should be replaced by a field
service technician.
Message
Action
System over temperature for CPU x.
1. Ensure that the system is being properly cooled; see
“System reliability considerations” on page 17.
2.
Replace microprocessor x.
Blade Storage Expansion option over
recommended temperature.
1. Ensure that the system is being properly cooled; see
“System reliability considerations” on page 17.
2.
Replace the SCSI hard disk drives.
3.
Replace the Blade Storage Expansion option.
CPU x over temperature.
1. Ensure that the system is being properly cooled; see
“System reliability considerations” on page 17.
2.
Replace microprocessor x.