ibaBM-DP
Manual
Issue 1.7
87
Basic settings
Locked, Enabled, Name, Modul No., Timebase
(only display),
Use name as pre-
fix
see chap. 10.3.1.1.
Profibus
Bus number
The bus on ibaBM-DP which is being monitored with this module.
10.3.7.2 „Analog“ tab
On the “Analog” tab, you find a series of predefined diagnostic values:
Counter corrupt frame
Shows the number of the detected, incomplete telegrams. The counter is a Byte
value revolving between 0 - 255.
Transmission rate
Detected transmission rate of the PROFIBUS in Mbit/s.
Bus cycle time
Measured bus cycle time in ms.
Number of masters
Number of the master stations detected on the PROFIBUS.
Number of slaves in exchange mode
Number of the slaves detected on the PROFIBUS which are exchanging data (Ex-
change Mode).
Number of active slaves
Number of slaves enabled on the device.
Number of missing slaves
Number of slaves which are configured on the PROFIBUS, but are missing.
Number of phantom slaves
Number of phantom slaves
Fig. 56: “Bus diagnostics” module – “Analog” tab