For detailed notes on the factory settings, please see chapters 9.2.1 (network) and 9.3.1
(password).
Note
The device must not be switched off during this procedure.
7.3.4
Rotary switches S1 and S2
The operating modes (rotary switch S1) and the device address (rotary switch S2) are
being set with the rotary switches.
S1
S2 ibaNet
protocol
Data volume / timebase
Note
Compatibility mode 3Mbit
0
0
3Mbit
64A + 64D in 1 ms
Up to 2 slaves
no sniffer function
Compatibility mode 32Mbit
1
0
32Mbit
512A + 512D in 1 ms
Max. data volume of analog values:
1984 Bytes
Sniffer fu up to 8
active slaves
Redundancy mode* can
be used
32Mbit Flex mode
1 1…F 32Mbit Flex 1024A + 1024D
Max. data volume depends on time-
base
Max. possible data volume: 4060
Bytes at 1.4 ms timebase
Min. timebase: 0.5 ms at max. possi-
ble data volume of 1540 Bytes
Sniffer fu up to 8
active slaves
Redundancy mode* can
be used
P2P mode
4
0
32Mbit
Simulation mode*
5
0
Not used
Mirror mode*
6
0
32Mbit
See compatibility mode 32Mbit
Sniffer function, no active
slaves
6 1…F 32Mbit Flex See 32Mbit Flex mode
Sniffer function, no active
slaves
Mapping mode*
7
0
Not used
No data acquisition possi-
ble
* additional license required
yellow: delivery state (with S2 = 1)