![IBA PROFIBUS ibaBM-DP Скачать руководство пользователя страница 142](http://html1.mh-extra.com/html/iba/profibus-ibabm-dp/profibus-ibabm-dp_manual_3210857142.webp)
Manual
ibaBM-DP
142
Issue 1.7
Fig 111:
Example how to transfer a consistent range of 32 byte from S7 PLC
(DB11) to ibaBM-DP using SFC15
3.
In your program you have to adjust the peripheral output address in network 3
(LADDR-parameter) with the DP output addresses in the HW configuration (column
Q Address).
Note
Do not forget the offset of the data set in the PROFIBUS message.
Example: In order to address the first analog value in mode 3, please consider an offset
of 8 Bytes / 4 Words.
For more information see chapter 13.2.4.1 „Output data “.
Fig 112: PLC S7 hardware configuration, PROFIBUS slave address space
4.
Now, download all modified blocks to PLC.