Manual
ibaBM-DP
132
Issue 1.7
13.2.5 Mode 5 – INPUT 32 Integers
This mode is used to write up to 32 integer values and 32 digital signals to the PROFIBUS
(IN 72 Bytes/OUT 4 Bytes).
13.2.5.1 Output data
OUTPUT DATA
Byte no.
Offset
Contents
Remark
1
0
Status
not used
2
1
Status
not used
3
2
Status
not used
4
3
Status
not used
13.2.5.2 Input data
INPUT DATA
Byte no.
Offset
Contents
Remark
1
0
FO message counter-A
incremented by each new FO message
2
1
FO reception status
Bit 7
:FO reception OK;
Bit 3
: 0 = integer, 1 = real
3
2
7 6 5 4 3 2 1 0 Dig. inputs channel 0...7
4
3
15 14 13 12 11 10 9 8 Dig. inputs channel 8...15
5
4
23 22 21 20 19 18 17 16 Dig. inputs channel 16...23
6
5
31 30 29 28 27 26 25 24 Dig. inputs channel 24...31
7
6
MSB
Analog input channel 0
Integer (2 byte), Big Endian Motorola
8
LSB
9
8
MSB
Analog input channel 1
Integer (2 byte), Big Endian Motorola
10
LSB
12
Analog inputs in total:
32 Words (16-bit integer), Big Endian Motorola
69
68
MSB
Analog input channel 31
Integer (2 byte), Big Endian Motorola
70
LSB
71
70
Device-ID of FO transmitter see list of iba device-IDs
72
71
FO message counter-B
incremented by each new FO message
13.2.5.3 GSD File
GSD file name
Remark
ibaF00n4.gsd
Transfer in one block with SFC (S7-400)
ibaF00n3.gsd
Transfer in three blocks with SFC (S7-300)
13.2.5.4 Applications
ibaLogic
System coupling
SIMATIC S7
SIMATIC TDC
SIMADYN D