13.2.6 Mode 6 – INPUT 32 Reals
This mode is used to write up to 32 real values and 32 digital signals to the PROFIBUS
(IN 136 Bytes/OUT 4 Bytes).
13.2.6.1 Output data
OUTPUT DATA
Byte no.
Offset
Contents
Remark
1
0
Status
not used
2
1
Status
not used
3
2
Status
not used
4
3
Status
not used
13.2.6.2 Input data
INPUT DATA
Byte no.
Offset
Contents
Remark
1
0
FO message counter-A
incremented by each new FO message
2
1
FO reception status
Bit 7
:FO reception OK;
Bit 3
: 0 = integer, 1 = real
3
2
7 6 5 4 3 2 1 0 Dig. inputs channel 0...7
4
3
15 14 13 12 11 10 9 8 Dig. inputs channel 8...15
5
4
23 22 21 20 19 18 17 16 Dig. inputs channel 16...23
6
5
31 30 29 28 27 26 25 24 Dig. inputs channel 24...31
7
6
MSB
Analog input channel 0
Real (4 byte), Big Endian Motorola
8
9
10
LSB
11
10
MSB
Analog input channel 1
Real (4 byte), Big Endian Motorola
12
13
14
LSB
14
Analog inputs in total:
32 Longs (Real), Big Endian Motorola
131
130
MSB
Analog input channel 31
Real (4 byte), Big Endian Motorola
LSB
135
134
Device-ID of FO transmitter see list of iba device-IDs
136
135
FO message counter-B
incremented by each new FO message
13.2.6.3 GSD File
GSD File name
Remark
iba_0F06.gsd
-
13.2.6.4 Applications
ibaLogic
System coupling
SIMATIC TDC
NO SIMATIC S7 (FW < 2.0 for S7-300, FW < 3.0 for S7-400), SIMADYN D