Page 51
8.5
Replacing Thermo Sensor (for Heater Ele-
ment)
Removal
»
Remove and open the steam cylinder as described
above in section “Removing and Cleaning the Steam
Cylinder.”
»
Loosen clips of capillary tube (T).
»
Disconnect capillary (T) tube from the heater elements
(8).
»
Remove the two screws (S) of thermo sensor (O).
»
Remove thermo sensor.
O: Thermo Sensor
P: Unlocking Button for Thermo Sensor
Q: Seal
R: Steam Cylinder
S: Screw
T: Capillary tube
Warning
: Do not bend the capillary tube of the thermo sensor!
Installation
»
Install thermo sensor with new sealing. Do not fix the
screws too tightly!
»
Neatly connect the capillary tube to the heater element.
Having humidifiers with two or more heating elements
the capillary tube is connected to two heating elements.
»
To proceed further, follow the steps described above in
section “Removing and Cleaning the Steam Cylinder -
Assembly“.
O
P
Q
R
S
T