Note:
•
Install the steam manifold horizontal with it ensure a clean
steam out.
•
Maximum allowable pressure in the air duct is 1200 Pa.
•
On the return side, the maximum allowable negative air
pressure is 500 Pa. Placement of the steam manifold on
the supply side of the air duct is preferred.
•
With high-pressure air-conditioning systems, the unit's
drain hose system must be modified depending on the
over pressure. When this is the case please consult
HygroMatik.
•
Install the steam manifold as close as possible to the
steam humidifier in order to minimize steam loss through
condensation.
•
Depending on the design of the air duct, additional moun-
ting of the steam manifold may be required. Shown instal-
lation and position dimensions are based on experimental
values. Special environmental conditions could require
adjustments.
•
We note that the German Association of Engineers (VDI)
Guideline 6022 specifies a water drain within the absorp-
tion distance inside the air duct.
•
For steam bath applications: Install the steam manifold
safe from contact with people in order to prevent injuries or
burns. Do not install the steam manifold near a tempera-
ture sensor or inaccurate readings may result.
•
Air flow rates over 3m/s can possibly lead to condensate
drainage problems at the steam manifolds which may
require adaptation measures.
Length of steam manifold [mm]*:
* special lenght on request
Note:
At lengths of 600mm or more, steam manifolds are
shipped with an extra alternative mounting fixture (Nut, M8) on
the closed end.
l
220
400
600
900
1200
1450
DN25
x
x
x
x
x
x
DN40
x
x
x
x
x
x