Water Discharge
Warning:
Please pay attention to free and non-pressure drain-
age of the water! During blow down up to 0.3L/s is being
drained. For water discharge, we recommend installation of a
flexible water drain hose. Humidifier and waste water discharge
must be on the same pressure level.
Please note:
•
The water drainage takes place directly through the
drain hose (23) which is connected to the pipe bends.
•
Do not bend drain hose.
•
For the discharge line and/or drain pipe, select materi-
als temperature-resistant up to 95°C.
6.5
Checklist
Verify correct system installation using the checklist below:
Can flushed-out water drain freely?
Have all screws and clamps been properly tightened?
Is the water supply line properly flushed out?
Has the water installation been performed correctly?
Is the drainage system correctly installed?
Are the water supply and drain lines free of leaks?
Warning:
Flush out the water supply line before connecting to
the solenoid valve, especially when installing a new line. This
prevents dirt particles from damaging the solenoid valve.