Page 38
7.1
Electrical Installation
»
Breakers must have a contact gap of at least 3 mm per
pole.
»
Connect potential equalization inside the unit to the
external ground bolt (located on the underside of the
cabinet beside the cable connections).
Observe European Directives shown in chapter „EC Declaration
of Conformity.
We recommend using a main fuse with medium blow rating
(applies only to the mains voltages above.) See table below indi-
cating maximum power consumption corresponding to each type
of circuit protection:
7.2
Safety Interlock
Between terminal 1 and 2 of the humidifier the so called safety
interlock is located. If the safety interlock is not closed the
humidifier is not allowed to work.
Any additional safety devices (see below) have to be installed
between those terminals. The safety interlock is also used for an
On/Off control mode (remote switch).
There is no electrical bridge between terminal 1 and 2 ex works.
If neither a Remote Switch nor any safety devices are wired to
terminal 1 and 2 an electrical bridge has to be set.
Note:
Install contact interlocks, i.e. max. hygrostat, vane relay,
pressure controller, air interlock etc. in series between Terminals
1 and 2.
Type
Power Supply
Power Con-
sumption
Fuses
HC02 Kit
230V/1Phases/N
6,5 A
1x10 A
HC03 Kit
230V/1Phases/N
9,8 A
1x10 A
HC06 Kit
230V/1Phases/N
19,6A
1x20 A
HC06 Kit
400V/3Phases/N
11,3A
3x16 A
HC12 Kit
400V/3Phases/N
19,5A
3x25 A
HC18 Kit
400V/3Phases/N
29,3A
3x35 A
HC27 Kit
400V/3Phases/N
29,3A
3x35 A
Terminals Humidifier
230V int.