Page 46
6.8.8 Functions submenu
Table of function parameters
14 Control_curve
Behaviour during cold start or specification for special applications (only ELDB [77]), see
[68]
0 Energie-optimized
Current during cold start is 128% of rated current for fast heating
1
Load-optimized
Current during cold start is 113% of the nominal current, to avoid overloading the supply
network despite fast heating
2 Process-optimized
Particularly fine control for critical applications
15 Delay_humidificat._notif.
Delay of "Humidifying" message in [s] (see [74])
No. Parameter
No.
Meaning/comment
[ ] explains the term in the glossary
min
max
FP
[ ] refers to a related term explanation
1 Standby-heating
The standby heating [16] keeps the water in the cylinder warm if no demand [5] is present
0
Off
Standby heating [16] switched off
1 On
Standby heating [16] switched on
2 Standby-heating_interval
Pause time of standby heating in [min]
3 Standby-heating_active
Heating time of standby heating [16] in [s]
4 Dead_leg_flushing
The solenoid valves of the water input and blow-down pump are switched on and off
simultaneously with the flushing of the dead-end line [27]
0
Deactivated
Flushing of dead-end line [27] is not carried out
1 Activated
Facilitate flushing of dead-end line [27]
5 Dead_leg_flushing_interval
Waiting period until start of flushing of dead-end line [27] in [min]
6 Dead_leg_flushing_active
Duration of flushing of dead-end line [27] in [s]
7 Runtime_limitation
Steam production is stopped after the time interval specified [min]
8 Weekly_timer
Activation of weekly timer
Steam production runs continously with the parameters preset
Steam production is only active in time periods preset in the "Weekly timer" submenu
9 Timer_mode
The timer function [18] is triggered with an external button
0
Off
The timer function [18] is not available
1 Steam_off
Steam production stops after the timer has elapsed
2 ECO
The unit reverts to ECO mode [61] after the timer has elapsed
10 Timer_running_time
The runtime of the timer is given in seconds
11 Password_remote
Storage of a password with a maximum of 4 digits for remote access via the
communication interface, input using the keyboard screen
12 Function_digital_input
Mapping of digital input function [98] to mainboard
0
Off
Not used
1 Push_button_light 1
Activated digital input [97] by a pushbutton [106] switches on light 1
2 Push_button_light 2
Activated digital input [97] by a pushbutton [106] switches on light 2
3 Push_button_light 3
Activated digital input [97] by a pushbutton [106] switches on light 3
4 Push_button_light 4
Activated digital input [97] by a pushbutton [106] switches on light 4
10 ECO
Activated digital input [97] by a pushbutton [106] switches ECO mode on
20 Steam_boost
Activated digital input [97] by a pushbutton [106] triggers steam jet [60]
30 Timer_start
Activated digital input [97] by a pushbutton [106] starts timer function [18]
40 Power_limitation
Activated digital input [97] by a switch (NO) switches power limitation on for load shedding
[101]
13 Power_retention
0
50
0
Reduction of humidifier performance after target temperature has been reached, to
proportion of maximum performance [%] entered here as power retention [66]
14 Control_curve
Behaviour during cold start or specification for special applications (only ELDB [77]), see
[68]
0 Energie-optimized
Current during cold start is 128% of rated current for fast heating
1
Load-optimized
Current during cold start is 113% of the nominal current, to avoid overloading the supply
network despite fast heating
2 Process-optimized
Particularly fine control for critical applications
15 Delay_humidificat._notif.
Delay of "Humidifying" message in [s] (see [74])
Adjustment/value range
Factory presets (FP)