6.8.2 Reading values submenu
The reading values submenu is no different
to that of the user level. The reading values
listed in table format in Section 6.6.2 are also
available at the operator level.
6.8.3 Control submenu
Table of control parameters
No. Parameter
No.
Meaning/comment
[ ] explains the term in the glossary
[ ] refers to a related term explanation
1 Control_settings
Combinations of control type and input signal type/range
0 User_specified
The selection was carried out separately during initial operation according to control type,
signal type and area. This is a read value only
7 1-step
1 step operation [44]
10 PI controller
Control with internal PI controller [96]
min
max
FP
2 Steam_output_max.
25,0
100,0
100
The maximum output power [43] can be limited to between 25 and 100%
3
∆
Power_reduction
0
50,0
0
Reduction of the maximum steam output for the purpose of load shedding [101]
4 Output_signal
Mapping of the output signal [69] to an internal value
0
Off
No mapping
2 Control_sig._internal
Output signal is proportional to the internal actuator signal [42]
4 Control_signal_slave
Output is used to control a slave [94]
Adjustment/value range
Factory presets (FP) bold