Page 64
122
Max.-level (only HKDB)
Water level has reached its
maximum 5x in one single
steam production phase
•
Excessive air pres-
sure in duct has impact
on water in steam cyl-
inder via steam hose.
Water is pressed into
drainage
•
Reduce air pres-
sure, check steam
hose for blockages
•
Solenoid valve clos-
ing action imperfect.
Cylinder water level
rises though solenoid
valve is not energised
•
Check solenoid valve
•
Solenoid valve is
permanently energised
(water intake stops
when unit is switched
off)
•
Relay contacts on
mainboard stick. Mea-
sure voltage across
terminal 11 and N; re-
place mainboard, if re-
quired
•
Large amounts of
residues influence or
restrict cyclic blow-
down. The additional
water introduction
caused by the optional
HyFlush rinse device
may cause the max.
level fault
•
Clean steam cylinder,
cylinder base, water
sensor tubing and
drainage system
These icons
are flashing
Fa
ult
code
Fault message
Possible cause
Measure