7.3 Functional fault chart
Possible
condition
Possible cause for fault situation
Countermeasure
Accumulation of
water on the floor
panel
•
Cylinder assembled incorrectly after
maintenance:
- O-ring damaged, not replaced or
- not inserted.
- Flange (tongue / groove) damaged.
- Flange not closed properly.
-
Scale deposits in flange.
•
Clean cylinder and install it
properly.
•
The cylinder is placed incorrectly in the
base.
•
Insert new moistened O-ring
into the base and then insert the
cylinder.
•
When pumping out, the water can not
drain freely.
•
Ensure free drainage.
Water leaks from
the top part of the
steam cylinder.
•
Hose clamps for steam or condensate
hoses do not close.
•
Tighten the hose clamps.
•
Steam hose adapter is not inserted cor-
rectly or O-ring has not been replaced.
•
Replace O-ring and install
steam hose adapter properly.
No steam produc-
tion, even though
the steam gener-
ator is switched
on and the dis-
play is active
•
Interlock (safety) system open
•
Close Interlock (safety) system
•
•
The temperature set value specified has
been reached, so that the control does
not receive a demand for steam produc-
tion.
Little air exchange; steam bath tempera-
ture remains above the programmed set
value for a long time
•
•
Check set value settings, check
the plausibility of the
temp._actual value.
Provide for sufficient air ex-
change by adjusting fan perfor-
mance
No steam produc-
tion. Voltage is
applied to the
electrodes, but no
water is fed in
(ELDB only)
•
Water supply is not open or solenoid
valve is not electrically controlled
•
Open water supply
see also
Fault filling
(fault
codes 030, 032)
The temperature
specified is not
reached
•
The max. steam output specified pre-
vents full power output
Check the
"Steam_output_max." parame-
ter and change setting, if re-
quired
.
•
Nominal power output not sufficient
•
Check technical data an the
amount of air (check secondary
amount of air as well)
•
A long steamhose laying through cold
and drafty rooms may lead to increased
condensation
•
Install unit in a different location
that allows a shorter steam-
hose. Insulate steamhose.
•