Page 43
Table of service parameters
3 Update
The parameter set is updated
4 Successful
The update was successful
5
USB stick does not contain a parameter set or parameter set is not compatible
31 Main_relay_on/off
Targeted function test
0
Off
1 On
3 Update
The parameter set is updated
4 Successful
The update was successful
5
USB stick does not contain a parameter set or parameter set is not compatible
31 Main_relay_on/off
Targeted function test
0
Off
1 On
No. Parameter
No.
Meaning/comment
[ ] explains the term in the glossary
[ ] refers to a related term explanation
1 Steam_amount_service
Preset steam volume (see [33]) in kg until service message is triggered. For double cylinder
units, this setting applies to both cylinders
4 Service-reset_cyl. 1
Reset steam volume counter for cylinder 1
[33]
0
Off
No
1 On
Yes
5 Steam_until_msg._cyl. 1
Remaining steam volume for cyl. 1 until service message
[33]
is triggered
7 Service-reset_cyl. 2
Reset steam volume counter for cylinder 2
[33], double cylinder units only
0
Off
No
1 On
Yes
8 Steam_until_msg._cyl. 2
Remaining steam volume for cyl. 2 until service message
[33]
is triggered
12 Main_contactor 1_reset
Reset K1 counter for main contactor operating cycles?
[34]
0
Off
No
1 On
Yes
13 K1_switching_cycles_until_msg.
Remaining operating cycles for K1 until service message
[34]
is triggered
14 Main_contactor 2_reset
Reset K2 counter for main contactor operating cycles?
[34]
0
Off
No
1 On
Yes
15 K2_switching_cycles_until_msg.
Remaining operating cycles for K2 until service message
[34]
is triggered
16 Main_contactor 3_reset
Reset K3 counter for. main contactor operating cycles?
[34] (double cyl. units only)
0
Off
No
1 On
Yes
17 K3_switching_cycles_until_msg.
Remaining operating cycles for K3 until service message
[34]
is triggered
18 Main_contactor 4_reset
Reset K4 counter for main contactor operating cycles?
[34] (double cyl. units only)
0
Off
No
1 On
Yes
19 K4_switching_cycles_until_msg.
Remaining operating cycles for K4 until service message
[34]
is triggered
20 Main_contactor 5_reset
Reset K5 counter for main contactor operating cycles?
[34] (double cyl. units only)
0
Off
No
1 On
Yes
21 K5_switching_cycles_until_msg.
Remaining operating cycles for K5 until service message
[34]
is triggered
22 Warning_cyl._full
Warning message about electrode burn-off (only for ELDB [77])
[95]
0 Off
No message
1 Sensitivity 1
Threshold value 1 for message (lowest sensitivity)
2 Sensitivity 2
Threshold value 2 for message (medium sensitivity)
3
Sensitivity 3
Threshold value 3 for message (highest sensitivity)
23 Warning_pump
Warning message about functional performance of blow-down pump
[95]
0 Off
No message
1 Sensitivity 1
Threshold value 1 for message (lowest sensitivity)
2 Sensitivity 2
Threshold value 2 for message (medium sensitivity)
3
Sensitivity 3
Threshold value 3 for message (highest sensitivity)
24 Warning_valve
Warning message about functional performance of solenoid valves
[95]
0 Off
No message
1 Sensitivity 1
Threshold value 1 for message (lowest sensitivity)
2 Sensitivity 2
Threshold value 2 for message (medium sensitivity)
3
Sensitivity 3
Threshold value 3 for message (highest sensitivity)
26 Update_function
Status of update function [7]
0
USB-stick_insert
USB stick is not inserted
1 Loading
The parameter set which is saved on the stick is loaded
2 Checking
The loaded parameter set is checked
Adjustment/value range
Factory presets (FP) bold
Содержание FLE TSPA Series
Страница 1: ...FlexLine Spa Control FL TSPA EN FL TSPA EN E 8881168 Manual...
Страница 89: ...Page 89 This page intentionally left blank...
Страница 94: ...100 A Member of the group...