6.8.11 SPA submenu
Table of SPA parameters
No. Parameter
No.
Meaning/comment
[ ] explains the term in the glossary
min
max
FP
[ ] refers to a related term explanation
1 Temp._set_value
20.0
49.0
45.0
Set value [3] of steam bath temperature
2 Temp._set_value
68
120,2
68,0
Set value [3] of steam bath temperature
3
∆
Temp._steam_on/off
.1
5.0
.5
The steam production is switched off when (temperature set value +
∆
temp. _steam_off)
has been reached.
4
∆
Temp._max.
1.0
10.0
10.0
Temperature set value [3] plus
∆
temp._max. results in absolute max. temperature [41], at
which the unit switches off for safety reasons
5 Steam_boost_blocking
60
600
60
Interval until the next steam jet is possible after a steam jet
[60]
6 Steam_boost_duration
0
300
20
Duration of a steam jet
[60]
7 ? Temp._steam_boost
1.0
5.0
1.0
Target temperature increase at steam jet activation
[60]
8 Light 1_initial_state
Determines the initial state of light 1 when unit is switched on
0
Off
Light switched off
1 On
Light switched on
9 Light 2_initial_state
Determines the initial state of light 2 when unit is switched on
0
Off
Light switched off
1 On
Light switched on
10 Light 3_initial_state
Determines the initial state of light 3 when unit is switched on
0
Off
Light switched off
1 On
Light switched on
11 Light 4_initial_state
Determines the initial state of light 4 when unit is switched on
0
Off
Light switched off
1 On
Light switched on
min
max
FP
12 Fan_run-on
0
120
0
Delay time [82] of all steam bath fans in automatic mode in min
13 Exhaust_fan1_mode
Operating mode of steam bath fan 1
0
Off
Off
1 On
Continuous operation, if unit control switch is in pos. "I"
2 Automatic
Steam bath fan is switched on when the target temperature has been reached [3] and
switched off again when (target temperature - steam bath fan 1_
∆
Temp.) has been reached
min
max
FP
14 Exhauts_fan1_
∆
temp.
0
5,0
0,5
Steam bath fan 1 is switched off when target temperature [3] + steam bath fan 1_
Δ Temp.
has been reached
15 Exhaust_fan2_mode
Operating mode of steam bath fan 2
0
Off
Off
1 On
Continuous operation, if unit control switch is in pos. "I"
2 Automatic
The steam bath fan is switched on when the target temperature has been reached [3] and
switched off again when (target tempe steam bath fan 2_
∆
Temp.) has been
reached
min
max
FP
16 Exhauts_fan2_
∆
temp.
0
5.0
.5
Steam bath fan 2 is switched off when target temperature [3] + steam bath fan 2_
Δ Temp.
has been reached
17 Supply_fan1_mode
Operating mode of steam bath fan 1
0
Off
Off
1 On
Continuous operation, if unit control switch is in pos. "I"
2 Automatic
tempe steam bath fan 1_
∆
Temp.) has been reached
Adjustment/value range
Factory presets (FP)
bold
min
max
FP
18 Supply_fan1_
∆
temp.
0
5.0
.5
Temperature difference above set value which must be achieved for steam bath fan 1 to be
switched off