Page 58
Entries on the unit info screen
5 Cycles_main_contactor 4
The maximum number of operating cycles for K4 has been reached and a
Service_main_contactor [34] is required
6 Cycles_main_contactor 5
The maximum number of operating cycles for K5 has been reached and a
Service_main_contactor [34] is required
12 Warning_electrodes
The electrode wear is very advanced (only for ELDB [77])
13 Warning_pump
A loss of functional performance has occurred in the area of the blow-down pump(s)
14 Warning_solenoid_valve
A loss of functional performance has occurred in the area of the solenoid valve(s)
No. Parameter
No.
Meaning/comment
[ ] explains the term in the glossary
min
max
FP
[ ] refers to a related term explanation
1
Fault_message_unit
Fault messages
0 No_fault
No error
1 Plug_ST09
The plug for the current transformer (ELDB [77]) or the level control (HKDB [78]) is not
attached
2 Cylinder_extension 1
There is a problem with the expansion board (double cylinder units only)
6 Relay_extension 1
There is a problem with relay board 1
7 Relay_extension 2
There is a problem with relay board 2
29 Internal
System error
30 Filling_valve 1
Fault solenoide valve 1 [19]
32 Filling_valve 1 a. 2
Fault solenoide valve 1 and solenoide valve 2 [19]
61 Part._blow-down
Partial blow-down [21] not successful
62 Full_blow-down
Full blow-down [22] not successful
63 Blow-down_dilution
Dilution [23] was not successful (only for ELDB [77])
64 Max._current_blow-down
Overcurrent blow-down [24] was not successful (only for ELDB [77])
65 Max._level_blow-down
Max. level blow-down [25] was not successful (only for HKDB [78])
66 Standby_blow-down
Stand-by blow-down [26] not successful
67 Start_blow-down
Start blow-down [20] not successful
90 Cylinder_full
Sensor electrode reports cylinder full status [38] for 60 min (only for ELDB [77])
91 Current_measurement
Value provided by current measurement not plausible (only for ELDB [77])
92 Main_contactor_current
A current is measured for at least 15 s, even though the main contactor [72] is not
actuated (only for ELDB [77])
93 Main_contactor_cyl._full
A cylinder full status [38] was detected for at least 15 s, even though the main
contactor [72] is not actuated (only for ELDB [77])
120 Thermoswitch
A thermo sensor [31] has been triggered (only for HKDB [78])
121 Water_level_sensor
Value provided by level control [39] not plausible (only for HKDB [78])
122 Max.-level
Max. level [40] was reached 5 times in a row during filling (HKDB [78] only)
123 Steam_down_time
Despite a current feed to the radiators, the water level has not changed in the period
specified
[53] (only for HKDB [78])
124 Relay_main_contactor
The relay for the control of the main contactor is not functioning correctly
240 Temp._sensor_miss
Temperature sensor, cable or input level defective with error pattern "High resistance"
241 Temp._sensor_broken
Temperature sensor, cable, or input level defective with error pattern "Short circuit"
242 Temperature_max
Max. temperature [41] exceeded
243 Temp._sensor 2_miss
Temperature sensor 2, cable or input level defective with error pattern "High
resistance"
244 Temp._Sensor 2_broken
Temperature sensor 2, cable or input level defective with error pattern
"Short circuit"
245 Temp._deviation
The two temperature sensors report different results
2
Fault_message_cyl. 1
see above
3
Fault_message_cyl. 2
see above
5
Service_message_cyl. 1
Cylinder 1 service message
0 No_service_msg.
A service is not required
1 Steam_amount_counter
A unit service is required due to the steam volume counter
2 Cycles_main_contactor 1
The maximum number of operating cycles for K1 has been reached and a
Service_main_contactor [34] is required
3 Cycles_main_contactor 2
The maximum number of operating cycles for K2 has been reached and a
Service_main_contactor [34] is required (only double cylinder units)
12 Warning_electrodes
The electrode wear is very advanced (only for ELDB [77])
13 Warning_pump
A loss of functional performance has occurred in the area of the blow-down pump(s)
14 Warning_solenoid_valve
A loss of functional performance has occurred in the area of the solenoid valve(s)
6
Service_message_cyl. 2
Text
Cylinder 2 service message (double cylinder units only)
0 No_service_msg.
A service is not required
1 Steam_amount_counter
A unit service is required due to the steam volume counter
4 Cycles_main_contactor 3
The maximum number of operating cycles for K3 has been reached and a
Service_main_contactor [34] is required
Adjustment/value range
Factory presets (FP)
bold