Page 45
6.8.6 Blow-down submenu
Table of blow-down parameters
6.8.7 Fill parameters submenu
Table of fill parameters
No. Parameter
No.
Meaning/comment
[ ] explains the term in the glossary
min
max
FP
[ ] refers to a related term explanation
1 Full_blow-down_correction
-5
5
0
Correction value for frequency of full blow-down ("+" = more frequently, "-" = less frequently)
[55]
2 Part._blow-down_correction
-5
5
0
Correction value for frequency of partial blow-down ("+" = more frequently, "-" = less
frequently)
[55]
3
Standby_blow-down
Full blow-down [58] for hygiene reasons, if there was no steam production
[26] for an
extended period
0
Off
No stand-by blow-down
1 On
Blow-down after waiting period
4 Standby_blow-down_interval
After the waiting period specified, the remaining water is pumped off if the interlock (safety)
system [11] was opened during this period of time, i.e. no steam production took place
[26]
5 Blow-down_without_K1
Pumps without main contactor [75] in order to avoid triggering of residual current detector
[56]
0
Off
Main contactor [75] switched on during pumping
1 On
Main contactor [75] switched off during pumping
Adjustment/value range
Factory presets (FP) bold
No. Parameter
No.
Meaning/comment
[ ] explains the term in the glossary
min
max
FP
[ ] refers to a related term explanation
1 Filling_pulsed
The filling process is not continuous, but intermittent
[54]
0
Off
Activated
1 On
Not activated
2 Filling_pulsed_interval
1
10
2
Time interval in s, during which filling does not take place (filling pause)
3 Filling_pulsed_active
1
600
10
Duration of filling time in s until filling pause
Adjustment/value range
Factory presets (FP) bold