Fuses and
Fuse Blocks
Supplied When
Required
7
10
8
11
9
12
13
16
14
17
15
18
19
20
21
25
26
27
29
30
28
25
28
26
29
27
30
19
22
20
23
21
24
1
2
3
TC-6
TC-5
TC-4
TC-3
Ambient Temperature Control of All Banks of Fans With
Pressure Override of the First Cycling Fan Bank for 2, 3, 4, or 5 Fan Bank Condenser
1
Terminal Block - Heavy Duty
Fuse Holder
Terminal Block - Medium Duty
Thermostat Control
Motor (Inherently Protected)
Replacement Parts
Figure A-8
Line Voltage Thermostatic with
Pressure Override Fan Control
Control Settings
Number of
Thermostats
Cut-In Settings for Thermostats – Deg F
2
3
4
5
TC-1
80
80
80
80
TC-2
75
75
75
75
TC-3
–
55
65
70
TC-4
–
–
50
55
TC-5
–
–
–
40
Refrig
R-404A
R-22
R-507
Cut-In
229
193
236
Cut-Out
203
168
210
PC-1 Settings – psig
Individual Motor FLA
HP
3/4
1
208/3/60
3.5
4.4
230/3/60
3.2
4.0
460/3/60
1.6
2.0
1
2
3
4
5
6
7
10
8
11
9
12
19
22
20
23
21
24
13
16
14
17
15
18
25
28
26
29
27
30
Set Cut-Out 5 Deg Below Cut-In
Total FLA Nunber of Motors = Applicable Motor FLA
TC-1
PC-1
Pressure Control
TC-2
PC-2
Figure 5-9 — Line Voltage Thermostatic
with Pressure Override Fan Control
Return to Contents