Minimum Allowable Distances
From a Water Cooled Condenser Outlet to the
Scroll Plus Receiver Inlet, the minimum allow-
able elevation is 1 foot.
With no Flooding Valve, the minimum allowable
distance is 4.5 feet from the mounting surface of
the air cooled Condenser to the mounting surface
of the Scroll Plus Rack.
With a Flooding Valve, the minimum allowable
distance is 6 feet from the mounting surface of the
air cooled Condenser to the center of the flooding
valve.
Maximum Allowable Distances
Remote Satellites should not be placed below the
level of the Scroll Plus Rack. The Satellite may be
positioned above the Rack. The maximum allow-
able elevation is 6 feet from the bottom of the
Satellite to the bottom of the Rack.
When piping from the Rack to a Remote Satellite,
the maximum allowable piping equivalent is
50 feet.
When piping from the Rack to a Remote Header,
the maximum allowable piping equivalent is
50 feet.
When piping from the Rack to a Condenser, the
maximum allowable piping equivalent is 100 feet.
When piping from the Rack to a Heat Reclaim
coil, the maximum allowable piping equivalent is
50 feet.
INSTALLATION INSTRUCTIONS
September 1, 1997
1 - 4
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
Condenser
Piping Equivalent 50 ft Max
Condenser
Piping Equivalent 50 ft Max
6 ft Min
6 ft Max
ScrollPlus Rack
Remote Satellite
Remote Header
Flooding
Valve
Field-Installed
Water Cooled
Condenser
1 ft Min
Piping Equivalent 100 ft Max
W/O Flooding Valve
4.5 ft Min
W/ Flooding Valve
Figure 1-3 — Allowable Distances
Return to Contents