FUSE, 5A on circuit board
can only be replaced
by removing board from panel. Remove the screw
on the front and on the top of the faceplate.
J1
through
J5 Jumpers
should be clipped for the
following conditions:
J1
if thermostat controls EPR solenoid
J2
for Koolgas defrost
J3
and
J1
for Off-time/Electric defrost (Do not
clip
J1
if suction stop EPR is used.)
J4
if mechanical defrost time clock is used
J5
if Fibertronic Defrost Clock 1000 is used
T-STAT
is input for temperature control thermo-
stat.
TEMP TERM
is input from defrost termination
thermostat – closes to end defrost.
X1
and
X2
are 120VAC input to the board and
defrost branch. X1 is Line and X2 is Neutral
.
KR
is output to Koolgas Relay
KG/3W SOL
is output to the Koolgas or 3-Way
Valve Solenoid, depending on which is applied.
EPR CNTR
is input from case thermostat when
controlling the suction stop solenoid for tempera-
ture. J1 must be cut.
EPR SOL
is output to the suction stop solenoid
valve.
LIQ BRANCH SOL
is output to the liquid
branch solenoid valve.
Q2
is fiber optic input from Fibertronic Defrost
Clock 1000.
September 1, 1997
P/N 401789
4 - 21
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
Figure 4-18 Defrost Board Inputs and Outputs
(View—removed from panel, faceplate held in left hand.)
2
1
2
1
2
1
T1
T11
T10
T5
T6
T7
T3
T2
T9
T8
Q2
T4
F1
5 AMP
J1
J2
J3
J4
J5
120 VAC
X2
X1
KOOLGAS/3W
SOL
EPR
CNTR
EPR SOL
LIQ BRANCH
SOL
T-STAT
MECH
DEFR
CLOCK
TEMP
TERM
K R
Figure 4-16 — Defrost Board Inputs and Outputs
(View—removed from panel, faceplate held in left hand.)
Return to Contents