Schematics show Sequence of Operation.
Electronic circuit logic is omitted, since printed
circuits are not field repairable.
Sequence of Operation
Control Panel 120V circuit closes
Power to
X1
energizes Alarm Relay (AR)
AR Electronic Circuit energizes
AR Coil
AR Contacts open
between Terminals
34
and
36
after Fuse F1
AR Contacts close
between Terminals
34
and
35.
The closed Compressor Alarm Circuit inputs 120V
at Terminal
COMP.
If the circuit opens
AR Coil DE-energizes
AR Contacts open
between Terminals
34
and
35.
AR Contacts close
between Terminals
34
and
36
after Fuse F1
Energizing
Alarm Light, Bell Stop Switch,
Terminals
31
and
32.
The A9 and T9A circuits remain open during normal
operation. If either circuit closes a 120V input to the
Alarm Board activates A9 or T9A LED and Alarm
Condition.
AR Coil DE-energizes
AR Contacts open
between Terminals
34
and
35.
AR Contacts close
between Terminals
34
and
36
after Fuse F1
Energizing
Alarm Light, Bell Stop Switch,
Terminals
31
and
32.
With A9 or T9A the Board will remain in Alarm
until the Reset is pressed or power turn off/turn on
is used.
The Bell Stop Relay (BSR) circuit may operate only
during Alarm Conditions. When the Bell Stop Switch
is closed
BSR Electronic Circuit energizes
BSR Coil
BSR Contacts open
the circuit to Terminal
32
BSR Contacts close
the circuit for its own power supply.
September 1, 1997
P/N 401789
4 - 3
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
X1
X2
COMP
A9
T9A
33
31
35
34
36
32
AR
AR
BSR
Alarm Reset
A9
T9A
Power
Line
Neutral
Alarm on
circuit open
Alarm on
circuit close
(3 Min Delay)
Alarm on
circuit close
(30 Min Delay)
BSR Coil
R
R
R
Inputs
Rack
Remote Light
Remote Bell
Remote
Alarm
Circuit
Common
Opens on Alarm
Closes on Alarm
Fuse
F1
(All schematics are
shown DE-energized.)
ALARM
LIGHT
BELL
STOP
AR
Electronic
Circuit
AR Coil
BSR
Electronic
Circuit
USING SCHEMATICS
Figure 4-1 — Alarm Board Circuits
Return to Contents