ELECTRICAL AND PRELIMINARY
CHECK-OUT
The following electrical diagrams show the inter-
nal wiring. Consult motor serial plate for wire
sizes.
After wiring is complete check condenser opera-
tion in the following manner prior to compressor
start-up.
1. Be sure the disconnect at the condenser is open,
then turn on power to the condenser at the store
distribution panel. Bypass the fan cycling con-
trols so all fans will operate.
2. Close the condenser disconnect and check the
fans for proper operation. The fans should dis-
charge air from the top of the condenser.
Reverse the rotation of any fans blowing in the
wrong direction. If the condenser is equipped
with gravity dampers, check that they open and
close freely. After fans check out, place the
fan-cycling controls back into operation.
Caution:
Before entering any fan section,
make sure power to the fan motors is discon-
nected.
3. Check that the proper winter condensing pres-
sure control has been applied as follows:
a: When more than one compressor unit is
connected to the same condenser, all fan
banks except the one nearest the discharge
and liquid manifolds must be cycled by
thermostats. each compressor unit must
also be equipped with condenser flooding
valves.
b. When only one compressor unit is con-
nected to a condenser, either of two types
of controls can be used: (1) thermostatic
fan-cycling of all fan banks with a pres-
sure-control override of the first cycling
fan bank (requires flooding controls), or
(2) Control B pressure controlled fan-
cycling of all fan banks and gravity
dampers for each fan (flooding controls
may be required in severe winter climate).
4. Adjust controls to the settings specified on the
wiring diagram. These are approximate settings
and may be changed to suit local conditions.
5. Leave condenser disconnect closed and turn off
power at the store distribution panel.
Evacuate, leak test, charge and start each system
according to the start-up section.
REMOTE SATELLITES & CONDENSERS
September 1, 1997
5 - 10
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
Return to Contents